        Your present location:产品首页 >> Products & service >> Oil Immersed Transformer >> single phase pole mounted transformer >> single phase pole mounted transformer
        • Product: single phase pole mounted transformer
        • 产品编号: D11
        • Views : 132

        Friends Recommend

        Features:

        1. Dtandards: GB1094-1996; JB/T10088-2004; GB/T6451-2008; EQV IEC 60076
        2. Capacity Range: 5-160kVA

        3. Primar Voltage : 2400-34,500 V               .Secondary Voltage: 120-600 V
        4. Voltage Regukation Mode: Off circuit tap changing
        5. tapping Range: ±5%, ±2×2.5%
        6. Frequency: 50Hz; 60Hz
        7. Phase: Single phase
        8. Connection Sign: II0; II6
        9. Short Circuit Impedance: Standard impedance (For details see technical data sheet)

         

        Core features

        Available option of Envirotemp FR3 fluid for increased fire safety or electrical grade mineral oil

        Meets or exceeds industry standards including ANSI, NEMA and DOE Energy Efficiency

        Constructed with EPRI-recommended interlaced core-type design for greater resistance to low-side voltage surges

        ●Polymer low-voltage bushings are standard at 5-50 kVA

        ●Cores and coils designed for high reliability and low field failure rates

        ●Domed cover design and formed cover band provide increased pressure withstand capability, eliminate bushing overhang and improve cover retention

        High-voltage bushing design improves gasket protection and seal

         

        The safer, environmentally friendly choice

        Single-phase conventional transformers can be filled with optional Envirotemp FR3 fluid, which provides increased fire safety and superior environmental characteristics where less-flammable fluid is desired. Because the fluid is readily biodegradable and non-toxic, Envirotemp fluid provides sustainable performance at a low cost.

         


        Technical Data of 10kV D9 Series Distribution Transformer
          Voltage Group(kV)   Loss (kW) No-load current Impedance Weight (kg) Outline Dimension (mm) Gauge
        Rated Capacity Connection Method 
        (L) (W) (H)  
        (kVA) HV LV   No-load Load % % Machine Oil Gross Dimension Vertical Horizontal
        5       35 145 4 3.5 50 40 130 530 450 850 400 250
        10       55 260 3.5 65 40 150 560 450 870 400 300
        16 11     65 365 3.2 80 40 180 600 450 920 400 300
        20 10.5     80 430 3 100 50 205 620 450 940 400 300
        30 10 0.22 li0 100 625 2.5 115 50 225 700 450 980 400 300
        40 0.24 li6 125 775 2.5 150 55 270 700 480 970 400 300
        50 6     150 950 2.3 175 70 310 650 510 1100 400 300
        63 6.3     180 1135 2.1 190 80 340 660 520 1100 400 300
        80       200 1400 2 240 100 420 770 630 1120 450 300
        100       240 1650 1.9 295 100 490 840 600 1150 450 300
        125       285 1950 1.8 370 110 560 890 740 1160 500 400
        160       365 2365 1.7 430 130 650 950 790 1170 500 400
        (Note): (Tapping range of high voltage) ± 5%; ± 2× 2.5%, Frequency: 50Hz.

         

        Product Uses

        The single-phase pole-mounted distribution transformers are specifically designed for the decentralization distribution network of servicing residential overhead distribution loads of town and countryside. They are also suitable for light and diversified power applications. These transformers are designed for the application conditions normally encountered on electric utility power distribution systems.

          参数1  
          Model Number